Voltage Drop Calculator
Voltage Drop Calculator calculates a circuit's voltage drop, in volts and percent, from current, circuit length, conductor cross-section and material (single-phase or three-phase). Use it to check whether the supply voltage remains adequate over long cable runs.
How it works
- 1Choose the phase type: single-phase or three-phase.
- 2Enter the current, circuit length (one-way distance) and conductor cross-section.
- 3Select the conductor material (copper/aluminum) and supply voltage.
- 4Read the voltage drop in volts and percent.
Frequently asked questions
Why does the circuit length count double (single-phase)?−+
Current travels from source to load and back through the neutral/return conductor, so total conductor length is twice the one-way distance. Three-phase uses a √3 factor instead (from the balanced three-phase system geometry).
What's an acceptable voltage drop percentage?−+
Most electrical codes suggest an upper limit of roughly 3% for lighting circuits and 5% for power circuits (typically 5% total from supply point to outlet); check your local code for the exact limit.
Why does voltage drop increase with aluminum instead of copper?−+
Aluminum's electrical resistivity is roughly 60% higher than copper's (0.0282 vs 0.0175 Ω·mm²/m); at the same cross-section and current, aluminum cable causes more voltage drop.
Is temperature effect accounted for?−+
No, a fixed resistivity value (roughly a 20°C reference temperature) is used; conductor resistance rises at higher temperatures, so the actual drop could be somewhat higher.
Is the data I enter stored anywhere?−+
No, the entire computation runs in your browser.
Embed on your site
<iframe src="https://toolsqube.com/en/electrical-engineering/voltage-drop-calculator/embed" width="480" height="360" style="border:0;border-radius:14px" title="Voltage Drop Calculator · ToolsQube" loading="lazy"> </iframe>
Want to go deeper on this topic: Electrical Circuit Tools Guide →